| Plan Review Notes For Permit 14090650 |
| Permit Number |
14090650 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-02 09:56:41 | 1ST REVIEW: FBC 2010 | | | | | | R302.1 EXTERIOR WALLS. | | | CONSTRUCTION, PROJECTIONS, OPENINGS AND PENETRATIONS OF | | | EXTERIOR WALLS OF DWELLINGS AND ACCESSORY BUILDINGS | | | SHALL COMPLY WITH TABLE R302.1, FIRE-RESISTANT | | | CONSTRUCTION. | | | WITHIN 3', 1 HOUR-TESTED IN ACCORDANCE WITH ASTM E 119 | | | OR UL 263 WITH EXPOSURE FROM BOTH SIDES | | | THE FLORIDA GLASS WALL PROPOSED AT 1'0" FROM THE | | | PROPERTY LINE IS DOES NOT MEET THE ABOVE REQUIREMENT | | | AND DOES NOT APPEAR TO QUALIFY FOR EXCEPTION 7 AS | | | FOLLOWS: " SCREEN ENCLOSURE WALLS OF INSECT SCREENING | | | WITH A MAXIMUM OF 25 PERCENT SOLID FLEXIBLE FINISHES." | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|