2014-09-19 09:10:54DATE: 9/18/2014
 PROJECT: ST ANNS CHURCH
 PERMIT#: 14090619
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A LOAD CALCULATION TO INDICATE THE TOTAL
 CONNECTED LOAD BELOW THAT OF THE EQUIPMENT RATING
 INCLUDING THE METER. WPB AMENDMENTS TO FBC 107.3.5, NEC
 110.3, 220.12, 220.14, 230.31
  
 2) PROVIDE THE NUMBER AND SIZE OF WIRE FOR ALL FEEDERS
 AND BRANCH CIRCUITS AFFECTED BY THE SCOPE OF WORK. WPB
 AMENDMENTS TO FBC 107.3.5,
  
 3) PROVIDE THE LOCATION OF THE A/C UNITS AND INDICATE
 THE REQUIRED DISCONNECTS. WPB AMENDMENTS TO FBC 107.3.5
  
 4) INDICATE THE LOCATION OF THE FPL VAULT AND THE
 BURIAL DEPTH FOR THE UNDERGROUND SERVICE LATERAL. WPB
 AMENDMENTS TO FBC 107.3.5, NEC 300.5
  
 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  