| 2014-09-19 09:10:54 | DATE: 9/18/2014 |
| | PROJECT: ST ANNS CHURCH |
| | PERMIT#: 14090619 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A LOAD CALCULATION TO INDICATE THE TOTAL |
| | CONNECTED LOAD BELOW THAT OF THE EQUIPMENT RATING |
| | INCLUDING THE METER. WPB AMENDMENTS TO FBC 107.3.5, NEC |
| | 110.3, 220.12, 220.14, 230.31 |
| | |
| | 2) PROVIDE THE NUMBER AND SIZE OF WIRE FOR ALL FEEDERS |
| | AND BRANCH CIRCUITS AFFECTED BY THE SCOPE OF WORK. WPB |
| | AMENDMENTS TO FBC 107.3.5, |
| | |
| | 3) PROVIDE THE LOCATION OF THE A/C UNITS AND INDICATE |
| | THE REQUIRED DISCONNECTS. WPB AMENDMENTS TO FBC 107.3.5 |
| | |
| | 4) INDICATE THE LOCATION OF THE FPL VAULT AND THE |
| | BURIAL DEPTH FOR THE UNDERGROUND SERVICE LATERAL. WPB |
| | AMENDMENTS TO FBC 107.3.5, NEC 300.5 |
| | |
| | 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |