| Plan Review Notes For Permit 14090554 |
| Permit Number |
14090554 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-20 04:58:58 | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 1) THE GAS PIPING FOR THE FIRE PIT IS NOT SHOWN ON THE | | | GAS RISER. SHOW THE PIPNG FOR THE FIRE PIT & BTU LOAD | | | ON THE DRAWING. | | | 2) SIZE ALL SECTIONS THE PIPING ON THE GAS RISER. | | | 3) SUBMIT A COPY OF THE APPLICABLE SIZING TABLE USED | | | FOR THE GAS SYSTEM. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND | | | LABELED PER THE 2010 FUEL GAS CODE SEC. 301.3. | | | 5) THERE ARE TWO LONGEST LENGTHS SHOWN ON THE PLANS. IT | | | APPEARS THAT THE LONGEST LENGTH IS THE RUN TO THE | | | WADING POOL HEATER. THIS LENGTH SHALL BE USED FOR THE | | | SIZING OF THE ENTIRE SYSTEM PER THE 2010 FGC | | | SEC.402.4.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|