| 2014-09-16 16:50:55 | DATE: 9/16/2014 |
| | PROJECT: BUS SHELTER |
| | PERMIT#: 14090549 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE THE MINIMUM PLAN REVIEW CRITERIA, RISER |
| | DIAGRAM, PANEL SCHEDULE, LOAD CALCULATION. |
| | |
| | 2) INDICATE HOW THE DESIGN IS PROPOSED TO COMPLY WITH |
| | THE FBC-E 505 LIGHTING FOR ALL EXTERIOR APPLICATIONS |
| | NOT EXEMPTED IN SECTION 505.1 SHALL HAVE AUTOMATIC |
| | CONTROLS CAPABLE OF TURNING OFF EXTERIOR LIGHTING WHEN |
| | SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING |
| | IS NOT REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |