| Plan Review Notes For Permit 14090539 |
| Permit Number |
14090539 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-16 14:01:11 | DATE: 9/16/2014 | | | PROJECT: ADS DIRECT | | | PERMIT#: 14080726 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) MAINTAIN STRUCTURAL AND FIRE RATING INTEGRITY OF | | | FLOOR WHEN PENETRATING WITH FLOOR BOXES. USE APPOVED | | | FIRE RATED POKE THROUGH BOXES. NEC, 110.3, 314.27(C) | | | | | | 2) MAINTAIN SEPARATION OF POWER AND DATA/COM CABLING | | | WHEN INSTALLING FLOOR BOXES. USE BOXES APPROVED FOR | | | THIS USE. NEC, 110.3, 314.27(D) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|