2014-09-16 14:01:11DATE: 9/16/2014
 PROJECT: ADS DIRECT
 PERMIT#: 14080726
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) MAINTAIN STRUCTURAL AND FIRE RATING INTEGRITY OF
 FLOOR WHEN PENETRATING WITH FLOOR BOXES. USE APPOVED
 FIRE RATED POKE THROUGH BOXES. NEC, 110.3, 314.27(C)
  
 2) MAINTAIN SEPARATION OF POWER AND DATA/COM CABLING
 WHEN INSTALLING FLOOR BOXES. USE BOXES APPROVED FOR
 THIS USE. NEC, 110.3, 314.27(D)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  