2014-09-17 11:45:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 ALL FLOOR SHEETS SHOW A STROBE IN EACH OF THE
 BATHROOMS. THE HORN DECIBEL LEVEL SHALL MEET THE
 MINIMUM REQUIREMENT OF NFPA 72 IN EACH BATHROOM ON EACH
 FLOOR. A FIRE INSPECTOR SHALL VERIFY AND CONFRIM ON
 INSPECTION.
  
 IS THERE A SPRINKLER HEAD AT THE TOP OF THE ELEVATOR
 HOISTWAY? IF SO, PLEASE PROVIDE A SMOKE DETECTOR PER
 NFPA 72.
  
 PLEASE PROVIDE A COPY THE CERTIFICATE OF COMPLETION AND
 TESTING TO THE FIRE INSPECTOR AT THE TIME OF FINAL
 INSPECTION.