| Plan Review Notes For Permit 14090535 |
| Permit Number |
14090535 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-17 11:45:55 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | ALL FLOOR SHEETS SHOW A STROBE IN EACH OF THE | | | BATHROOMS. THE HORN DECIBEL LEVEL SHALL MEET THE | | | MINIMUM REQUIREMENT OF NFPA 72 IN EACH BATHROOM ON EACH | | | FLOOR. A FIRE INSPECTOR SHALL VERIFY AND CONFRIM ON | | | INSPECTION. | | | | | | IS THERE A SPRINKLER HEAD AT THE TOP OF THE ELEVATOR | | | HOISTWAY? IF SO, PLEASE PROVIDE A SMOKE DETECTOR PER | | | NFPA 72. | | | | | | PLEASE PROVIDE A COPY THE CERTIFICATE OF COMPLETION AND | | | TESTING TO THE FIRE INSPECTOR AT THE TIME OF FINAL | | | INSPECTION. |
|