| 2014-10-31 17:28:00 | | | | ***REVIEW IN PROGRESS.... | | | | | | | | | 1-SPECIFY ANCHOR TO BE USED. | | | | | | 2- SPECIFY THE EXISTING BEDROOM WINDOWS TYPE AND SIZE | | | TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF | | | SEC. 604 OF 2010 FBC-EXISTING BUILDING CODE. | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED | | | IN THE PERMIT APPLICATION. ACCORDING TO SKETCH | | | SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS | | | TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE | | | PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR, | | | MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS | | | REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE | | | VALUATION AS REQUIRED. | | | | | | | | | |
|