| 2014-10-07 10:56:46 | RESIDENTIAL (R3) WINDOW ALTERATION, SECOND BUILDING |
| | REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE. |
| | INFORMATION SHOWN IN THE SHUTTERS INSTALLATION SCHEDULE |
| | SUBMITTED IS INCOMPLETE. IT DOESN'T PROVIDE ANY |
| | INFORMATION CONCERNING THE PROPOSED INSTALLATION. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- SKETCH SUBMITTED: CLEARLY SPECIFY THE EXISTING |
| | BEDROOM WINDOWS TYPE AND SIZE TO VERIFY COMPLIANCE WITH |
| | THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010 |
| | FBC-EXISTING BUILDING CODE. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED |
| | IN THE PERMIT APPLICATION. ACCORDING TO SKETCH |
| | SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS |
| | TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE |
| | PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR, |
| | MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS |
| | REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE |
| | VALUATION AS REQUIRED. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |