| Notes |
| Date |
Text |
| 2014-09-16 16:15:21 | RESIDENTIAL (R2) ALTERATION BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC | | | | | | 1- PROVIDE INFORMATION FOR THE FLAME SPREAD INDEX AND | | | SMOKE DEVELOPED INDEX OF THE "SOUNDGUARD" INSULATION TO | | | BE INSTALLED. INFORMATION SUBMITTED TO BE IN ACCORDANCE | | | WITH ASTM E 84 OR UL 723 AS REQUIRED BY SEC. 719.1 OF | | | 2010 FBC. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND | | | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. | | | 109.3 OF CITY AMENDMENTS TO FBC. REVISE VALUATION AS | | | REQUIRED. | | | | | | ***IMPORTANT: | | | INFORMATION SUBMITTED SHOWS IIC RATING OF 71 AND STC | | | RATING OF 67. THESE RESULTS ARE BASED ON A FLOOR | | | ASSEMBLY OF 8" CONCRETE SLAB WITH SUSPENDED GYPSUM | | | CEILING OVERLAY. VERIFY THAT THAT FLOOR ASSEMBLY IN | | | THIS BUILDING MEETS THAT CRITERIA. OTHERWISE, | | | ADDITIONAL INFORMATION WILL BE REQUIRED TO MATCH ACTUAL | | | FLOOR ASSEMBLY IN THIS BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|