| 2014-09-13 10:02:48 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. MOISTURE SURVEY SHOWS UNACCEPTABLE MOISTURE LEVELS |
| | IN PORTIONS OF THE ROOF DECK. PERMIT APPLICATION STATES |
| | THIS IS A "REROOF" (REMOVAL OF EXISTING ROOF DOWN TO |
| | DECK, INSTALL NEW DECK) BUT THE PRODUCT APPROVAL |
| | SUBMITTED IS FOR A "RECOVER" (INSTALL A NEW ROOF OVER |
| | THE EXISTING ROOF). |
| | |
| | THE MOISTURE SURVEY SHOWS AREAS OF HIGH (UNACCEPTABLE) |
| | MOISTURE, BUT NO INFORMATION WAS PROVIDED AS TO HOW |
| | THIS WILL BE RESOLVED. SEE FBC 2010 EXISTING BUILDING |
| | 611.3(1), REMOVAL OF EXISTING ROOF REQUIRED WHRE THE |
| | EXISTING ROOF OR ROOF COVERING IS WATER SOAKED (SEE |
| | CODE FOR FULL TEXT OF THIS SECTION), |
| | |
| | 2. SEE FBC 2010 EXISTING BUILDING 611.1.1, NOT MORE |
| | THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION |
| | OF AN EXISTING BUILDING SHALL BE REPAIRED. ENGINEER IS |
| | TO DETERMINE THE PERCENTAGE OF EXISTING ROOF OR ROOF |
| | COVERING IS REQUIRED TO BE REPAIRED PRIOR TO THE |
| | PROPOSED RECOVER. |
| | |
| | 3. THIS ADDRESS HAS AN EXPIRED PERMIT, 08080132. IF IT |
| | IS DETERMINED THAT A REROOF IS REQUIRED RATHER THAN A |
| | ROOF RECOVER, A MECHANICAL PERMIT WILL BE REQUIRED AS |
| | WELL AS A DETAIL AS TO HOW THE MECHANICAL EQUIPMENT |
| | WILL BE INSTALLED, FBC 107, FBC 1509.7. |
| | |
| | TWO OF THE FOUR MECHANICAL UNITS ARE LOCATED IN AREAS |
| | OF UNACCEPTABLE MOISTURE. IF IT IS DETERMINED THAT |
| | THESE AREAS CAN BE REPAIRED, REINSTALLATION OF THE |
| | MECHANICAL EQUIPMENT MAY BE REQUIRED. IF THIS IS THE |
| | CASE, A MECHANICAL SUB PERMIT WILL BE REQUIRED AS WELL |
| | AS A DETAIL FOR INSTALLATION, FBC 1609, FBC 1509.7. |
| | |
| | |
| | |