Plan Review Notes
Plan Review Notes For Permit 14090429
Permit Number 14090429
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2014-12-31 13:26:586701 NORTH JOG ROAD - MAINTENANCE BUILDING
 PERMIT #14090429
 RACK #14080063
 MASTER #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 I AM NOT CONVINCED, BUT, REQUESTING A % DENSITY
 REDUCTION FOR STORAGE HEIGHTS BELOW 20 FEET (NFPA 13
 SECTION 16.2.1.3.4) MIGHT BE JUSTIFIED FOR THE CEILING
 SLOPE OF 11.8 DEGREES (2.5/12 OR 0.21); HOWEVER, HALF
 THE BUILDING UTILIZED FOR STORAGE HAS A CEILING SLOPE
 OF 16 DEGREES (3.25/12 OR 0.27). HIGH-PILED COMBUSTIBLE
 STORAGE COUPLED WITH A SLOPED CEILING (PITCH EXCEEDING
 2/12 OR 0.16) CAN GREATLY AFFECT THE QUANTITY AND THE
 LOCATIONS OF THE SPRINKLERS THAT MAY BE ACTIVATED
 DURING A FIRE EVENT. HIGH-PILED STORAGE WITHOUT A
 HORIZONTAL CEILING IS OUTSIDE THE SCOPE OF NFPA 13;
 THEREFORE, A PERFORMANCE-BASED ENGINEERING DESIGN IS
 NEEDED. IF FM DATA IS CHOSEN, THEN ALL THE REQUIREMENTS
 OF FM NEED TO BE FOLLOWED AND SUBMITTED. SELECTIVE
 REQUIREMENTS OR "CHERRY PICKING" WILL NOT BE SUPPORTED.
 THE ENGINEERING RESPONSE LETTER INDICATES, "FOR ROOF
 SLOPES GREATER THAN 10 DEGREES BUT LESS THAN 20
 DEGREES, FM SUGGESTS PROTECTION UNDER SUCH SLOPED ROOFS
 IS ACCEPTABLE PROVIDED THAT ONE LEVEL OF IN-RACK
 SPRINKLERS AND STANDARD RESPONSE CEILING SPRINKLERS ARE
 INSTALLED;" HOWEVER, NO FM DATA SHEET SECTION IS
 PROVIDED FOR REFERENCE. FM DATA SHEET 2-0, SECTION
 2.2.1.6 INDICATES THAT "STORAGE" SPRINKLERS ARE
 ACCEPTABLE UNDER SLOPED CEILINGS BETWEEN 10 AND 20
 DEGREES; HOWEVER, STORAGE SPRINKLERS BY FM STANDARDS
 HAVE A K-FACTOR GREATER THAN 8.0 (K=8.0 CURRENTLY
 INSTALLED CEILING SPRINKLERS).
  
 THE PLANS INDICATE SPRINKLERS/PIPING TO BE SUPPORTED
 BELOW THE MEZZANINE. PROVIDE A SIGNED/SEALED LETTER
 WITH LOAD CALCULATION INDICATING THE MEZZANINE
 STRUCTURE IS CAPABLE OF SUPPORTING THE WEIGHT OF WATER
 FILLED PIPING PLUS 250 POUNDS APPLIED AT THE POINT OF
 HANGING PER NFPA 13 SECTION 9.2.1.3.1.
  
 AN INSPECTION CONDUCTED 12/29/14 REVEALED 8 (VERIFY)
 FLAMMABLE LIQUID STORAGE CONTAINERS (CAPACITY: 90
 GALLONS EACH) LOCATED ADJACENT TO THE STORAGE
 MEZZANINE.
  
 WESLEY R. JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE STATION #1: 561.804.4752
 CONST. SERVICES : 561.805.6730
 [email protected]
  
  
  
  
 ORIGINAL COMMENTS:
 THE PLANS INDICATE A REQUIRED DENSITY OF 0.23
 GPM/SQ.FT. OVER 2500 SQ.FT. PER FIGURE 16.2.1.3.2(C)
 USING CURVE A; HOWEVER, CURVE A REQUIRES
 HIGH-TEMPERATURE CEILING SPRINKLERS. PER SPRINKLER
 PERMIT #12030242, THE CEILING SPRINKLERS ARE ORDINARY
 TEMPERATURE (155F). THE USE OF ORDINARY TEMPERATURE
 SPRINKLERS REQUIRES THE DESIGNER TO UTILIZE CURVE B OF
 FIGURE 16.2.1.3.2.(C). A DESIGN AREA OF 2500 SQ.FT.
 CORRESPONDS TO A DENSITY OF 0.26 GPM/SQ.FT.
  
 INDICATE WHAT MEANS/METHODS ARE IN PLACE TO LIMIT THE
 HIGH-PILED STORAGE TO 18.5 FEET ABOVE FINISHED FLOOR SO
 DENSITY CAN BE REDUCED TO 87% PER FIGURE 16.2.1.3.4.1.
  
 IN-RACK SPRINKLERS SHALL BE LOCATED AT AN INTERSECTION
 OF TRANSVERSE AND LONGITUDINAL FLUES WHILE NOT
 EXCEEDING THE MAXIMUM SPACING RULES.
  
 HAS AN INCREASED DESIGN AREA OR SKEWED OPERATING
 PATTERN BEEN CONSIDERED TO ACCOUNT FOR THE CEILING
 SLOPE EXCEEDING 2 IN 12? THE SPRINKLER SYSTEM CRITERIA
 SPECIFIED IN CHAPTER 12 AND CHAPTERS 14 THROUGH 20 ARE
 INTENDED TO APPLY TO BUILDINGS WITH CEILING SLOPES NOT
 EXCEEDING 2 IN 12 (16.7 PERCENT) PER NFPA 13 SECTION
 12.1.2 - CEILING SLOPE.
  
 PROVIDE A SPRINKLER DETAIL OR ELEVATION SHOWING THE
 SPRINKLER PLACEMENT WITHIN THE RACKS.
  
 NO HYDRAULIC CALCULATIONS SUBMITTED.
  
  
  
 EMAIL STRING FROM 11/12/14:
 FM DATA SHEET 2-0 INDICATES, "STORAGE SPRINKLERS ARE
 ACCEPTABLE UNDER SLOPED CEILINGS"; HOWEVER, THE
 CURRENTLY INSTALLED CEILING SPRINKLERS (RELIABLE MODEL
 F1, K-8.0 [SIN R1722] ARE NOT APPROVED AS STORAGE
 SPRINKLERS PER FM BECAUSE THEY HAVE A K-FACTOR OF 8.0.
 PLEASE SEE BELOW...
  
 FM DATA SHEET 8-9 (STORAGE OF COMMODITIES)
  
 2.3.3 CEILING-LEVEL STORAGE SPRINKLERS
  
 FM APPROVED SPRINKLERS FOR STORAGE OCCUPANCY HAZARDS
 AND OTHER SIMILAR HIGH HEAT-RELEASE TYPE FIRES ARE
 LISTED IN THE APPROVAL GUIDE, AN ONLINE RESOURCE OF FM
 APPROVALS, UNDER THE HEADING OF STORAGE SPRINKLERS
 (CEILING-LEVEL) OR STORAGE SPRINKLERS (IN-RACKS). THIS
 SECTION WILL DISCUSS RECOMMENDATIONS FOR FM APPROVED
 CEILING-LEVEL STORAGE SPRINKLERS.
  
 FOLLOW THE GUIDELINES IN DATA SHEET 2-0, INSTALLATION
 GUIDELINES FOR AUTOMATIC SPRINKLERS, FOR THE
 INSTALLATION OF CEILING-LEVEL STORAGE SPRINKLERS.
  
 USE ONLY FM APPROVED SPRINKLERS LISTED IN THE APPROVAL
 GUIDE UNDER THE HEADING OF STORAGE SPRINKLERS
 (CEILING-LEVEL) FOR ANY CEILING-LEVEL SPRINKLER OPTIONS
 IN THIS DATA SHEET. CURRENTLY, FM APPROVED
 CEILING-LEVEL STORAGE SPRINKLERS HAVE K-FACTOR VALUES
 RANGING FROM 11.2 TO 25.2. NOTE THAT THE FOLLOWING
 SPRINKLERS ARE NOT FM APPROVED AS CEILING-LEVEL STORAGE
 SPRINKLERS: K=8.0 AND SMALLER.
  
  
  