2014-10-01 16:33:446701 NORTH JOG ROAD - MAINTENANCE BUILDING
 PERMIT #14090429
 RACK #14080063
 MASTER #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE A REQUIRED DENSITY OF 0.23
 GPM/SQ.FT. OVER 2500 SQ.FT. PER FIGURE 16.2.1.3.2(C)
 USING CURVE A; HOWEVER, CURVE A REQUIRES
 HIGH-TEMPERATURE CEILING SPRINKLERS. PER SPRINKLER
 PERMIT #12030242, THE CEILING SPRINKLERS ARE ORDINARY
 TEMPERATURE (155F). THE USE OF ORDINARY TEMPERATURE
 SPRINKLERS REQUIRES THE DESIGNER TO UTILIZE CURVE B OF
 FIGURE 16.2.1.3.2.(C). A DESIGN AREA OF 2500 SQ.FT.
 CORRESPONDS TO A DENSITY OF 0.26 GPM/SQ.FT.
  
 INDICATE WHAT MEANS/METHODS ARE IN PLACE TO LIMIT THE
 HIGH-PILED STORAGE TO 18.5 FEET ABOVE FINISHED FLOOR SO
 DENSITY CAN BE REDUCED TO 87% PER FIGURE 16.2.1.3.4.1.
  
 IN-RACK SPRINKLERS SHALL BE LOCATED AT AN INTERSECTION
 OF TRANSVERSE AND LONGITUDINAL FLUES WHILE NOT
 EXCEEDING THE MAXIMUM SPACING RULES.
  
 HAS AN INCREASED DESIGN AREA OR SKEWED OPERATING
 PATTERN BEEN CONSIDERED TO ACCOUNT FOR THE CEILING
 SLOPE EXCEEDING 2 IN 12? THE SPRINKLER SYSTEM CRITERIA
 SPECIFIED IN CHAPTER 12 AND CHAPTERS 14 THROUGH 20 ARE
 INTENDED TO APPLY TO BUILDINGS WITH CEILING SLOPES NOT
 EXCEEDING 2 IN 12 (16.7 PERCENT) PER NFPA 13 SECTION
 12.1.2 - CEILING SLOPE.
  
 PROVIDE A SPRINKLER DETAIL OR ELEVATION SHOWING THE
 SPRINKLER PLACEMENT WITHIN THE RACKS.
  
 NO HYDRAULIC CALCULATIONS SUBMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE