2014-09-30 15:43:306701 NORTH JOG ROAD - MAINTENANCE BUILDING
 PERMIT #14090427
 RACK #14080063
 MASTER #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COULD NOT LOCATE PORTABLE FIRE EXTINGUISHERS ON MAIN
 FLOOR OR MEZZANINE LEVEL. TRAVEL DISTANCE TO
 EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEVERAL EMERGENCY LIGHT FIXTURES HAVE BEEN ADDED AROUND
 THE BUILDING INTERIOR PERIMETER; HOWEVER, NO DEVICS
 HAVE BEEN ADDED AT/BELOW THE MEZZANINE OR THE AISLES
 BETWEEN THE HIGH-PILED (18.5 FEET) STORAGE RACKS.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 ADDITIONAL ILLUMINATED EXIT SIGNS ARE NEEDED TO
 ACCOMODATE THE VISUAL OBSTRUCTIONS CREATED BY THE
 MEZZANINE AND HIGH-PILED STORAGE RACKS.
  
 SEPARATE PLANS AND PERMIT NEEDED FOR PAINT SPRAY BOOTH.
  
 A REQUEST FOR TCO HAS BEEN INDICATED; HOWEVER, THE
 PLANS INDICATE A REVISION TO THE BREAKROOM AND RESTROOM
 AREAS.
  