| Plan Review Notes For Permit 14090408 |
| Permit Number |
14090408 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-20 05:42:57 | CITY OF WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. | | | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | | GAS RANGE. | | | 2) THE GAS TABLE REFERENCED ON YOUR DRAWING SHOWS THE | | | CSST TUBING SIZES IN EHD (EQUIVALENT HYDRAULIC | | | DIAMETER). INDICATE THE CORRELATING EHD FOR THE NOMINAL | | | PIPE SIZES SHOWN ON THE GAS PIPING RISER. | | | 3)THE GAS PLAN INDICATES PIPING WILL BE RUN UNDER THE | | | HOUSE. GAS PIPING INSTALLED BENEATH FLOORS SHALL COMPLY | | | WITH SEC.404.12 OF THE 2010 FGC. SUBMIT A DETAIL FOR | | | THE TYPE OF CONDUIT TO BE INSTALLED, THE SIZE, THE | | | LOCATION, ETC. THE CONDUIT SHALL ORIGINATE AND | | | TERMINATE IN AN OCCUPIABLE/ACCESSIBLE PORTION OF THE | | | BUILDING. | | | 4) THE GAS RISER SHOWS CSST TUBING TO THE TANKLESS | | | WATER HEATER BUT THE PLAN SHOWS GALVANIZED PIPING. | | | CLARIFY. | | | 5) INDICATE THE TYPE OF VENT/CHIMNEY FOR THE TANKLESS | | | WATER HEATER. THE LOCATION OF THE VENT SHALL COMPLY | | | W/SEC. 503 OF THE 2010 FGC. | | | 6) IDENTIFY THE TANKLESS WATER HEATER OUTLET ON THE GAS | | | RISER. | | | 7) PLANS DRAWN IN PENCIL ARE NOT ACCEPTABLE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|