| Date |
Text |
| 2014-09-25 09:47:54 | BUILDING PLAN REVIEW |
| | PERMIT: 14090389 |
| | ADD: 309 CLEMATIS ST |
| | CONT: TBD |
| | TEL: (561)296-7699 SCOTT SMITH |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. SEPT. 25TH/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A EXIT PLAN FOR THE WHOLE BUILDING. |
| | PLEASE NOTE THIS IS A THREE STORY BUILDING A-2 / A3 |
| | ASSEMBLY BUILDING WITH ONLY 2 ENCLOSED STAIRWELLS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: A FLOOR PLAN; |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | |
| | 2) 2010 FBC-B 1016.1 DOES ALLOW FOR UNENCLOSED |
| | STAIRWELLS FOR 50 % OF EXITS BUT EXCEPTION # 3 ONLY |
| | ALLOWS THE EXIT ACCESS TRAVEL DISTANCE TO A MAXIMUM OF |
| | 50 PERCENT OF THE EXITS IS PERMITTED TO BE MEASURED |
| | FROM THE MOST REMOTE POINT WITHIN A BUILDING TO AN EXIT |
| | USING UNENCLOSED EXIT ACCESS STAIRWAYS OR RAMPS WHEN |
| | CONNECTING A MAXIMUM OF TWO STORIES. THE TWO CONNECTED |
| | STORIES SHALL BE PROVIDED WITH AT LEAST TWO MEANS OF |
| | EGRESS. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN |
| | TO OTHER STORIES. THIS STAIR CONNECTS TO THE 3RD STORY |
| | A ROOF TOP ASSEMBLY FLOOR. |
| | |
| | 3) NOTE THERE IS ALSO AN OPEN EXPIRED PERMIT FOR THE |
| | 3RD STORY ROOFTOP ADDITION, NEVER ACHIEVED A |
| | CERTIFICATE OF OCUPANCY, PERMIT # 08060519. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |