| 2014-09-26 14:03:53 | 1) SHT. AG- ACCESSIBILITY GUIDELINES - CHAPTER 6 | | | GUIDELINES - WATER CLOSETS AND LAVATORY CLEARANCES | | | DETAILS SHOW VERTICAL GRAB BARS. GRABS SHALL BE | | | INSTALLED IN A HORIZONTAL POSITION PER FL. ACCESS. CODE | | | SEC.609.4. VERTICAL GRAB BARS ARE NOT PERMITTED. ALSO, | | | SEE SHEETS A3.3 (R.R. ELEVATIONS) | | | 2) TOILET PAPER DISPENSERS SHALL BE 7"MINIMUM AND 9" | | | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE | | | CENTERLINE OF THE DISPENSER AND 15' MINIMUM AND 48" | | | MAXIMUM ABOVE THE FINISHED FLOOR AND NOT BE LOCATED | | | BEHIND GRAB BARS PER THE FAC SEC.604.7. | | | 3) SUBMIT A WATER AND SANITARY RISER DIAGRAM THAT | | | REFLECTS THE SCOPE OF WORK TO BE DONE PER SEC. | | | 107.3.5.1.3 OF THE 2010 WPB AMENDMENTS TO THE 2010 FBC. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|