| 2014-09-15 08:18:17 | DATE: 9/15/2014 |
| | PROJECT: EVERNIA PLACE |
| | PERMIT#: 14090358 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E |
| | 505.2.4. INDICATE ON THE PLANS THE INSTALATION AND USE |
| | OF A TIMECLOCK AND PHOTO SENSOR FOR CONTROL OF THE SIGN |
| | AND STREET LIGHTING CIRCUITS AND PER THE FBC-E 505.2.4. |
| | |
| | 2) THE GROUNDING ELECTRODE CONDUCTOR SHALL NOT BE LESS |
| | THAN GIVEN IN THE NEC TABLE 250.66. REVISE PLANS |
| | ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |