Notes
Date Text
2014-11-03 15:26:531) CLEANOUTS ARE REQUIRED IN THE BASE OF SOIL AND WASTE
 STACKS PER THE 2010 FBCR SEC.P3005.2.6. - 2ND REQUEST.
 2) THE LAYOUT OF THE FIXTURES ON THE SANITARY RISER
 DOES NOT CORRELATE WITH THE LAYOUT ON THE FLOOR PLAN,
 WPB AMEND. TO 2010 FBC SEC. 107.2.1. 2ND REQUEST.
 3) THE SANITARY RISER DIAGRAM SHOWS A FLAT, DRY VENT
 FOR THE FIRST FLOOR WATER CLOSET IN THE POOL BATH AND
 ALSO FOR THE SECOND FLOOR WATER CLOSET IN THE MASTER
 BATH. EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM
 OF SIX INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST
 TRAP OR TRAPPED FIXTURE BEIN VENTED BEFORE OFFSETTING .
 2010 FBCR, SEC. P 3104.4.
 4) SECOND FLOOR MASTER BATH - THE WASHING MACHINE IS
 NOT PERMITTED TO BE INSTALLED ON A HORIZONTAL WET VENT
 PER SEC.P3108.1 OF 2010 FBCR.
 5) THE 1 INCH INDIRECT WASTE PIPE FOR THE ICE MAKER IS
 NOT TO CODE. THIS DRAIN IS CONNECTED TO THE SANITARY
 SYSTEM THEREFOR SHALL BE TRAPPED & VENTED TO PREVENT
 SEWER GAS FROM ENTERING THE STRUCTURE. @010 FBCR
 SEC.P2706.1.
 6) DRAIN PIPING BELOW GRADE SHALL BE A MINIMUM OF 1
 1/2" PER FBCR P2903.5.
 7) SHOCK ARRESTORS SHALL BE INSTALLED ON THE ICE
 MACHINE, DISHWASHER AND WASHING MACHINE. FBCR
 SEC.P2903.5
 .
 GAS:
 8) THE SPECIFICATION SHEETS SUBMITTED FOR THE GAS
 GENERATOR & WATER HEATER DO NOT SHOW THAT THE
 APPLIANCES ARE LISTED AND LABELED IN ACCORDANCE WITH
 THE 2010 FBCR SEC.G2404.3.
 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR & VENT
 DETAILS.COMPLY W/ 2010 FBCRG (GAS) SECS. G2407.1,
 G2407.5, G2439.4.
 10) THE GENERATOR SHALL COMPLY W/ NFPA 37 FOR THE
 LOCATION AND ALSSO MEET UL 2200 STANDARD.
 11) NFPA 37 - SEC 4.1.4 - ENGINES SHALL BE 5 FT. FROM
 OPENINGS IN WALLS & 5 FT. FROM COMBUSTIBLE WALLS UNLESS
 THE WALL HAS A FIRE RESISTANCE RATING OF AT LEAST 1 HR.
 AND THE ENCLOSURE MUST BE OF NON- COMBUSTIBLE
 CONSTRUCTION.
 12) SHOW THE LOCATION OF THE GENERATOR EXHAUST ON THE
 PLAN. EXHAUST SHALL BE 10 FT. FROM BUILDING OPENINGS
 AND AIR INTAKE VENTS.
 13) THE SECTION OF P.E. GAS PIPING BETWEEN THE TEE FOR
 THE INTERIOR AND THE 2 PSI REGULATOR SHALL BE 1 " IN
 SIZE AS THE BTU LOAD IS 997,000. THE GAS SIZING TABLE
 NOTES THAT THE MAXIMUM BTU LOAD ON 3/4" PE PIPE IS
 860,000.
 14) SHT.A-0.1 - CLARIFY THE USE OF THE 1" TEE ON THE
 CSST PIPING RISER.
 15) SHOW THE LOCATION OF THE LOW PRESSURE REGULATOR
 (2ND STAGE ) REGULATOR FOR THE CSST. I NEED THIS INFO
 TO CHECK THE SIZING OF THE SYSTEM.
 16) THE CSST RISER CHANGES SIZE FROM THE REGULATOR FROM
 1/2 " TO 3/4" AND THEN BACK TO 1/2" AGAIN. CLARIFY.
 17) THE EHD OF THE CSST NEEDS TO BE 23 INSTEAD OF 19 TO
 HANDLE THE BTU LOAD.
  
 NOTE: YOU CAN PLACE A NOTE ON THE PLANS THAT "GAS TO BE
 UNDER SEPARATE PERMIT " AND YOU CAN ADDRESS THE GAS
 COMMENTS AT THAT TIME. YOU WILL HAVE TO REMOVE ALL THE
 GAS DRAWINGS FROM THIS PERMIT IF YOU CHOOSE TO DO SO.
 AS FOR THE PLUMBING COMMENTS,
 YOU MAY CALL ME TO DISCUSS THE COMMENTS OR WE CAN MEET