| Plan Review Notes For Permit 14090340 |
| Permit Number |
14090340 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-11-13 12:41:47 | 11/14/14 TALKED TO ALAN. HE SAID HE'LL WORK ON THE | | | PROVISO BEFORE ISSUING THE PERMIT. JG. | | | | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE ICC OR ANY OTHER APPROVED EVALUATION REPORT | | | (2 COPIES) FOR THE OPEN CELL FOAM INSULATION SPECIFIED | | | FOR NEW ROOF ATTIC ON WALL SECTION 3/A-07 TO VERIFY | | | COMPLIANCE WITH SEC. R316. | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR STRUCTURAL CONNECTOR TYPE "E" (PA 51) | | | SPECIFIED ON SHEET S-4. | | | 3- ENGINEER TO REVISE RAS 117 CALCULATIONS. THE | | | EFFECTIVE AREA FOR COMPONENTS AND CLADDING IS AT LEAST | | | 10 S.F. NOT 50 S.F. SEE NOTE "A" ON TABLE R301.2(2) OR | | | NOTE BELOW "NET DESIGN WIND PRESSURE" TABLE FROM FIGURE | | | 30.5-1 OF ASCE 7-10. | | | | | | | | | JULIO GOMEZ | | | (561)805-6712 | | | [email protected] |
|