2014-10-01 10:05:13WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) INDICATE ON THE PLAN IF THE FIREPLACE IS GAS OR WOOD
 BURNING.
 2) CLEANOUTS ARE REQUIRED IN THE BASE OF SOIL AND WASTE
 STACKS PER THE 2010 FBCR SEC.P 3005.2.6.
 3) THE LAYOUT OF THE FIXTURES ON THE SANITARY RISER
 DOES NOT CORRELATE WITH THE FLOOR PLAN.
 4) INDICATE THE SIZE OF ALL VTR'S ON THE SANITARY
 RISER.
 5)THE RISER DIAGRAM SHOWS A DRY VENT FOR THE 1ST FLOOR
 WATER CLOSET IN THE POOL BATH AND ALSO FOR THE 2ND
 FLOOR WATER CLOSET IN THE MASTER BATH. THE DRY VENT
 SHALL CONNECTTO THE HORIZONTAL DRAIN ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. 2010 FBCR SEC.
 P3104.3.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER, THE RANGE AND THE GAS GENERATOR.
 7) 2ND FLOOR M.B. - THE WASHING MACHINE IS NOT
 PERMITTED TO BE INSTALLED ON A HORIZONTAL WET VENT PER
 THE 2010 FBCR SEC.P3108.1.
 8) SIZE THE DRAIN FOR THE 2ND FLOOR WASHING MACHINE.
 9) SUBMIT INSTALLATION INSTRUCTIONS FOR THE EMERGENCY
 GENERATOR.
 10) SUBMIT A GAS DRAWING FOR THE GAS SYSTEM AND MANUF.
 SHEETS FOR ALL GAS EQUIPMENT.
  