| Plan Review Notes For Permit 14090340 |
| Permit Number |
14090340 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-01 10:05:13 | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 1) INDICATE ON THE PLAN IF THE FIREPLACE IS GAS OR WOOD | | | BURNING. | | | 2) CLEANOUTS ARE REQUIRED IN THE BASE OF SOIL AND WASTE | | | STACKS PER THE 2010 FBCR SEC.P 3005.2.6. | | | 3) THE LAYOUT OF THE FIXTURES ON THE SANITARY RISER | | | DOES NOT CORRELATE WITH THE FLOOR PLAN. | | | 4) INDICATE THE SIZE OF ALL VTR'S ON THE SANITARY | | | RISER. | | | 5)THE RISER DIAGRAM SHOWS A DRY VENT FOR THE 1ST FLOOR | | | WATER CLOSET IN THE POOL BATH AND ALSO FOR THE 2ND | | | FLOOR WATER CLOSET IN THE MASTER BATH. THE DRY VENT | | | SHALL CONNECTTO THE HORIZONTAL DRAIN ABOVE THE | | | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. 2010 FBCR SEC. | | | P3104.3. | | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATER, THE RANGE AND THE GAS GENERATOR. | | | 7) 2ND FLOOR M.B. - THE WASHING MACHINE IS NOT | | | PERMITTED TO BE INSTALLED ON A HORIZONTAL WET VENT PER | | | THE 2010 FBCR SEC.P3108.1. | | | 8) SIZE THE DRAIN FOR THE 2ND FLOOR WASHING MACHINE. | | | 9) SUBMIT INSTALLATION INSTRUCTIONS FOR THE EMERGENCY | | | GENERATOR. | | | 10) SUBMIT A GAS DRAWING FOR THE GAS SYSTEM AND MANUF. | | | SHEETS FOR ALL GAS EQUIPMENT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|