| Plan Review Notes For Permit 14090340 |
| Permit Number |
14090340 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-09 14:33:54 | 1. CHECK NOTES ON PLAN FOR AFCI PROTECTION PER N.E.C. | | | 210.12. PRIVATE PROVIDER NOTES STATES ARC FAULT | | | PROTECTION BEDROOM OUTLETS. ELECTRICAL NOTES ON PLAN | | | STATES ALL 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING | | | OUTLETS AS PER N.E.C. 210.12. | | | 2. ELECTRICAL NOTES ON PLAN STATES ELECTRICAL WORK | | | SHALL BE IN ACCORDANCE WITH THE 2013 N.E.C. CURRENTLY | | | ENFORCEMENT IS 2008 N.E.C. | | | 3. N.E.C. 210.63 RECEPTACLE OUTLET WITHIN 25' OF A.C. | | | EQUIPMENT. | | | 4. N.E.C. 210.8 (A)3. GFCI PROTECTION OUTDOOR | | | RECEPTACLES. | | | 5. N.E.C. 210.8 (A)1. GFCI PROTECTION PROTECTION ALL | | | BATHROOM RECEPTACLES. | | | 6. AHU UNIT #2 ON MECHANICAL PLAN SHOWS 5KW, PANEL | | | SCHEDULE "A" SHOWS 60 AMP OCPD. | | | 7. TABLE 310.15 (B)6. UNABLE TO USE THIS NOTE WITH | | | MULTIPLE SERVICE DISCONNECTS.( PLAN STATES SEPARATE | | | PERMIT)? | | | 8. N.E.C. 230.66. ATS SHALL BE IDENTIFIED AS SUITABLE | | | FOR USE AS SERVICE EQUIPMENT. | | | |
|