2014-10-09 14:33:541. CHECK NOTES ON PLAN FOR AFCI PROTECTION PER N.E.C.
 210.12. PRIVATE PROVIDER NOTES STATES ARC FAULT
 PROTECTION BEDROOM OUTLETS. ELECTRICAL NOTES ON PLAN
 STATES ALL 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS AS PER N.E.C. 210.12.
 2. ELECTRICAL NOTES ON PLAN STATES ELECTRICAL WORK
 SHALL BE IN ACCORDANCE WITH THE 2013 N.E.C. CURRENTLY
 ENFORCEMENT IS 2008 N.E.C.
 3. N.E.C. 210.63 RECEPTACLE OUTLET WITHIN 25' OF A.C.
 EQUIPMENT.
 4. N.E.C. 210.8 (A)3. GFCI PROTECTION OUTDOOR
 RECEPTACLES.
 5. N.E.C. 210.8 (A)1. GFCI PROTECTION PROTECTION ALL
 BATHROOM RECEPTACLES.
 6. AHU UNIT #2 ON MECHANICAL PLAN SHOWS 5KW, PANEL
 SCHEDULE "A" SHOWS 60 AMP OCPD.
 7. TABLE 310.15 (B)6. UNABLE TO USE THIS NOTE WITH
 MULTIPLE SERVICE DISCONNECTS.( PLAN STATES SEPARATE
 PERMIT)?
 8. N.E.C. 230.66. ATS SHALL BE IDENTIFIED AS SUITABLE
 FOR USE AS SERVICE EQUIPMENT.
  