| 2014-10-10 08:36:02 | RESIDENTIAL (R3) ALTERATION AND ADDITION, BUILDING |
| | REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SHEET A-02: |
| | A) MASTER BEDROOM WINDOW "F" ON THE WINDOW SCHEDULE ON |
| | SHEET A-04 STATES "MUST MEET EGRESS REQ FOR 5 SF MIN |
| | CLR OPNG". THE MIN. CLEAR OPENING ON A SECOND FLOOR |
| | BEDROOM WINDOW IS 5.7 S.F.. SEC. R310.1.1 OF 2010 |
| | FBC-RESIDENTIAL. REVISE SPECIFICATIONS AND PROVIDE |
| | MANUFACTURER'S CUT SHEETS SHOWING THAT THE PROPOSED |
| | WINDOW SIZE WILL PROVIDE THE MIN. REQUIRED CLEAR |
| | OPENINGS (WIDTH, HEIGHT AND TOTAL CLEAR OPENING). SEC. |
| | 107.2.1.3 OF CITY AMENDMENTS TO FBC. |
| | |
| | B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW AWNINGS (AND RELOCATED AWNINGS). SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | ***NOTE: OR SPECIFY IF COMPLETE INFORMATION WILL BE |
| | PROVIDED UNDER A SEPARATE PERMIT. |
| | |
| | C) NEW SECOND BEDROOM LOCATED ON THE SECOND LEVEL. SHOW |
| | COMPLIANCE THAT THE WINDOWS COMPLY WITH THE EGRESS |
| | REQUIREMENTS (HEIGHT, WIDTH AND TOTAL CLEAR OPENING) OF |
| | SEC. R310 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 2- PLANS ARE MISSING INFORMATION REGARDING THE EXTERIOR |
| | WALL COVERING: |
| | A) PROVIDE DETAILS/SPECIFICATIONS FOR THE STUCCO FINISH |
| | THICKNESS SHOWING COMPLIANCE WITH TABLE R702.1(1) OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE DETAILS/SPECIFICATIONS FOR THE STUCCO BOND |
| | BREAK SHOWING COMPLIANCE WITH SEC. R703.6.3 OF 2010 |
| | FBC- |
| | |
| | 3- SHEET A-03: SPECIFY SCUPPERS SIZES AND REVISE |
| | LOCATION OF EMERGENCY OVERFLOW SCUPPER TO SHOW |
| | COMPLIANCE WITH SEC. R903.4.1 OF 2010 FBC-RESIDENTIAL. |
| | EMERGENCY SCUPPER SHALL BE LOCATED CLOSE TO THE |
| | VERTICAL DOWNSPOUT. |
| | |
| | 4- PROPOSED WEST ELEVATION ON SHEET A-05: SPECIFY ATTIC |
| | VENT SIZES AND CLARIFY HOW THE TWO "CLAY ATTIC VENTS" |
| | ARE GOING TO PROVIDE CROSS VENTILATION AS REQUIRED BY |
| | SEC. R806 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: NEW 2X12 RAFTERS DON'T ALLOW CROSS VENTILATION |
| | AT THE NEW ROOF AREA. |
| | |
| | 5- SHEET S-4: |
| | A) PROVIDE THE DESIGN WINDOWS PRESSURES FOR ZONE #5. |
| | ONLY THE ZONE #4 WERE PROVIDED. SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | B) PROVIDE THE DESIGN PRESSURES FOR DOORS TO BE |
| | REPLACED. SEC. R301. |
| | C) SPECIFY DIMENSION "Z" ON THE FLAT ROOF . |
| | ***NOTE: THIS DIMENSION IS 4'-0" IN ALL CASES. SEE NOTE |
| | "A" OF FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL. |
| | C) PROVIDE THE DESIGN PRESSURES FOR SKYLIGHTS TO BE |
| | REPLACED. COORDINATE WITH ITEM #5(C) ABOVE. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SKYLIGHTS. NOA 13-1217.24 SUBMITTED WAS SUPERSEDED |
| | BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE AND |
| | DOWNLOAD CURRENT NOA. |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR. OR PROVIDE THE FLORIDA PRODUCT APPROVAL |
| | NUMBER ADJACENT TO EACH CONNECTOR SPECIFIED ON PLANS. |
| | |
| | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| | APPROVALS (INCLUDING THE ROOFING, SKYLIGHTS). AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 8- FLAT ROOF MODIFIED BITUMEN NOA 13-0424.14 SUBMITTED: |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | **** PLEASE REMOVE AND REPLACE ANY REVISED SHEET. |
| | **** PLEASE PROVIDE PLANS WITH PALM BEACH COUNTY IMPACT |
| | FEES STAMP AND PROVIDE COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |