| Plan Review Notes For Permit 14090331 |
| Permit Number |
14090331 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-11 13:54:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | | E 84 OR UL 723. | | | | | | IF THE MANUFACTURER AGREES TO HAVE THIS PRODUCT TESTED, | | | THE MANUFACTURER CAN EMAIL A LETTER ON LETTERHEAD | | | STATING THAT THEY WILL HAVE THE PRODUCT TESTED AND | | | STATE WHY THEY HAVE A REASONABLE EXPECTATION THAT THE | | | PRODUCT WILL PASS THE TEST. | | | | | | 2. THE SOUND TEST REPORTS WERE EXTREMELY POOR QUALITY. | | | THEY ARE SUFFICIENT FOR THIS PERMIT. HOWEVER, I AM NOW | | | MAINTAINING A FILE OF COMPLIANT TEST REPORTS TO GIVE TO | | | CONTRACTORS. IF LEGIBLE TEST REPORTS ARE EMAILED TO ME, | | | I'LL CREATE A FILE FOR THIS PRODUCT. | | | | | | | | | | | | |
|