Plan Review Notes
Plan Review Notes For Permit 14090321
Permit Number 14090321
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-10 12:20:28WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SUBMIT 2 COPIESOF THE MANUFACTURER'S SPECIFICATION
 SHEETS FOR THE TANKLESS WATER HEATER. THE WATER HEATER
 SHALL BE LISTED AND LABELED PER THE 2010 FL. GAS CODE
 SEC. 301.3.
 2) SUBMIT A GAS PIPING RISER FOR REVIEW. SHOW THE TYPE
 AND SIZE OF THE PIPING, THE BTU LOAD OF THE
 APPLIANCE,THE TOTAL DISTANCE FROM THE GAS POINT OF
 DELIVERY TO THE MOST REMOTE GAS OUTLET. THE PIPE SHALL
 BE SIZED IN ACCORDANCE WITH SECS.402.2 & 402.4, AND
 402.4.1. OF THE 2010 FL. GAS CODE.
 3) SUBMIT A COPY OF THE SIZING TABLE FROM THE FL. GAS
 CODE FOR THIS INSTALLATION.
 4) INDICATE THE SIZE OF THE WATER LINES TO THE HEATER
 ON THE PLAN.