Plan Review Notes
Plan Review Notes For Permit 14090314
Permit Number 14090314
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-29 10:50:571) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE PEDICURE CHAIRS.
 WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHOW THE CLEAR FLOOR SPACE REQUIRED FOR ALL THE
 FIXTURES ON BOTH SETS OF PLANS. THE CLEAR FLOOR SPACE
 SHALL COMPLY WITH THE 2010 FL. ACCESSIBILITY CODE
 SEC.305.1.
 3) THE REQUIRED CLEAR FOR SPACE FOR THE DRINKING
 FOUNTAIN SHALL BE CENTERED ON THE UNIT. FAC SEC.602.2.
 4) ONE OF THE HAND SINKS SHALL COMPLY W/ SECS.212.3 &
 606 OF THE 2010 FAC.
 5) THE WASHER & DRYER SHALL COMPLY W/2010 FAC
 SEC.611.2, 611.3, 611.4.
 6) SHT. P-1 - SIZE THE STUDOR VENTS ON THE NEW SANITARY
 DRAIN. VENT SIZE SHALL COMPLY W/TABLE 916.1 OF 2010 FL.
 PLUMBING CODE.
 7) CLEANOUTS ARE REQD. IN THE WASTE AND VENT STACKS PER
 2010 FPC SEC.708.3.4.
 8) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE PER THE 2010 FAC
 SEC. 603.2.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  