| Notes |
| Date |
Text |
| 2014-09-29 10:50:57 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION INSTRUCTIONS FOR THE PEDICURE CHAIRS. | | | WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SHOW THE CLEAR FLOOR SPACE REQUIRED FOR ALL THE | | | FIXTURES ON BOTH SETS OF PLANS. THE CLEAR FLOOR SPACE | | | SHALL COMPLY WITH THE 2010 FL. ACCESSIBILITY CODE | | | SEC.305.1. | | | 3) THE REQUIRED CLEAR FOR SPACE FOR THE DRINKING | | | FOUNTAIN SHALL BE CENTERED ON THE UNIT. FAC SEC.602.2. | | | 4) ONE OF THE HAND SINKS SHALL COMPLY W/ SECS.212.3 & | | | 606 OF THE 2010 FAC. | | | 5) THE WASHER & DRYER SHALL COMPLY W/2010 FAC | | | SEC.611.2, 611.3, 611.4. | | | 6) SHT. P-1 - SIZE THE STUDOR VENTS ON THE NEW SANITARY | | | DRAIN. VENT SIZE SHALL COMPLY W/TABLE 916.1 OF 2010 FL. | | | PLUMBING CODE. | | | 7) CLEANOUTS ARE REQD. IN THE WASTE AND VENT STACKS PER | | | 2010 FPC SEC.708.3.4. | | | 8) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR | | | CLEARANCE REQUIRED FOR ANY FIXTURE PER THE 2010 FAC | | | SEC. 603.2.3. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|