| 2014-09-10 16:26:39 | DATE: 9/10/2014 |
| | PROJECT: PETSMART PBLM |
| | PERMIT#: 14090269 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | FIRE INSPECTOR COMMENTS. |
| | 1) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS |
| | BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE |
| | DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS |
| | OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL |
| | ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN |
| | ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII", |
| | OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO |
| | MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM |
| | SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED |
| | MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO |
| | THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY. |
| | THE PROJECT IS DESIGNED AS A STAND ALONE FIRE ALRM |
| | SYSTEM. PROVIDE MANUFACTURER COMPATABILITY |
| | DOCUMENTATION TO SUPPORT THE FIRE INSPECTORS COMMENTS. |
| | |
| | 2) PROVIDE SUPPORTING DOCUMENTATION FOR THE |
| | CONTRACTOR'S $4,800.00 STATED VALUATION OF THE PROJECT. |
| | WPB AMENDMENTS TO THE FBC SECTION 109.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |