Plan Review Notes
Plan Review Notes For Permit 14090269
Permit Number 14090269
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-10 16:26:39DATE: 9/10/2014
 PROJECT: PETSMART PBLM
 PERMIT#: 14090269
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 FIRE INSPECTOR COMMENTS.
 1) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS
 BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE
 DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS
 OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL
 ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN
 ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII",
 OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO
 MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM
 SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED
 MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO
 THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY.
 THE PROJECT IS DESIGNED AS A STAND ALONE FIRE ALRM
 SYSTEM. PROVIDE MANUFACTURER COMPATABILITY
 DOCUMENTATION TO SUPPORT THE FIRE INSPECTORS COMMENTS.
  
 2) PROVIDE SUPPORTING DOCUMENTATION FOR THE
 CONTRACTOR'S $4,800.00 STATED VALUATION OF THE PROJECT.
 WPB AMENDMENTS TO THE FBC SECTION 109.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  