| Plan Review Notes For Permit 14090266 |
| Permit Number |
14090266 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-13 06:06:13 | WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. | | | 1) SUBMIT A GAS PIPNG RISER THAT CLEARLY REFLECTS THE | | | SCOPE OF WORK TO BE DONE. | | | 2) SHOW ALL THE APPLIANCES ON THE GAS RISER AND SHOW | | | THE BTU LOAD FOR EACH APPLIANCE. | | | 3) SHOW THE DISTANCE FROM THE POINT OF GAS DELIVERY TO | | | THE MOST REMOTE OUTLET. | | | 4) THE PLANS LIST 11 APPLIANCES BUT ONLY 3 SHUTOFF | | | VALVES ARE SHOWN ON THE GAS RISER. | | | 5) SHOW THE PIPE SIZES OF ALL THE PIPING ON THE GAS | | | RISER | | | 6) SUBMIT COPIES OF THE GAS SIZING TABLES FOR THE | | | GALVANIZED PIPING AND THE CSST TUBING. | | | 7) SUBMIT CLEAR AND LEGIBLE COPIES OF THE MANUF. SHEETS | | | FOR THE GAS DRYERS. | | | 8) THE DESCRIPTION OF WORK ON YOUR APPLICATION STATES | | | "CONNECT TO EXISTING FIXTURES" YET YOU HAVE SUBMITTED | | | SPEC SHEETS FOR WHAT APPEARS TO BE NEW EQUIPMENT. | | | CLARIFY. | | | 9) SHOW ON THE FLOOR PLAN WHERE THE UNDERGROUND GAS | | | PIPING IS TO BE ELIMINATED AND HOW THIS PIPING WILL BE | | | ABANDONED. |
|