| Date |
Text |
| 2014-09-18 17:02:19 | 4395 EASLEY DRIVE |
| | PERMIT #14090256 |
| | 90% SUBMITTAL REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | VOLUME 4 REVIEW: |
| | SHEET C-YPP-22: PROVIDE A SEPARATE DOMESTIC WATER LINE |
| | TAP FROM THE FIRE LINE TAP OR INDICATE THE GREATEST |
| | DOMESTIC WATER DEMAND TO BE EXPECTED SO THIS GPM DEMAND |
| | CAN BE ACCOUNTED FOR IN THE SPRINKLER SYSTEM HYDRAULIC |
| | CALCULATIONS. |
| | |
| | VOLUME 5 REVIEW: |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | SHEET A-DEW-05: FIRE RATED WALL INDICATORS ARE MISSING |
| | FROM STAIR #306, ELEVATOR, AND WALL ADJACENT TO |
| | EXTERIOR STAIR. |
| | |
| | SHEET A-DEW-28: OUTSIDE STAIRS MORE THAN 36 FEET ABOVE |
| | FINISHED GROUND LEVEL SHALL BE PROVIDED WITH OPAQUE |
| | VISUAL OBSTRUCTION NOT LESS THAN 48-INCHES IN HEIGHT TO |
| | ACCOMODATE PERSONS HAVING A FEAR OF HIGH PLACES PER |
| | NFPA 101 SECTION 7.2.2.6.2. |
| | |
| | SHEET A-DEW-25: DOOR #300 REFERENCES A NOTE #4 WHICH |
| | DOES NOT EXIST. |
| | |
| | GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE |
| | BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS. |
| | CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND |
| | HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT |
| | MORE THAN 15 FEET ON CENTER. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| | BUILDING ADDRESSES OR NAMES THAT ARE VISIBLE FROM THE |
| | STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO THE |
| | BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH |
| | 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. |
| | |
| | GENERAL: PROVIDE A PERMANENT WEATHERPROOF DIAMOND |
| | PLACARD PER NFPA 704 INDICATING THE HEALTH, |
| | FLAMMABILITY AND REACTIVITY RATING OF THE HAZARDOUS |
| | MATERIALS. |
| | |
| | ELECTRICAL ROOMS: PER NFPA 70 ARTICLE 110.26(C)(3) |
| | PERSONNEL DOORS. WHERE CONDUCTORS AND EQUIPMENT USED ON |
| | CIRCUITS ARE OVER 600 VOLTS OR EQUIPMENT IS RATED 1200 |
| | A OR MORE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING |
| | DEVICES, OR CONTROL DEVICES IS INSTALLED AND THERE IS A |
| | PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS |
| | FROM THE WORKING SPACE LESS THAN 25 FEET FROM THE |
| | NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL |
| | OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH |
| | PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE |
| | NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. |
| | CONFIRM CIRCUITS ARE NOT OVER 600 VOLTS AND EQUIPMENT |
| | IS NOT RATED 1200 A OR MORE. |
| | |
| | TOXIC FUMES: MOTOR VEHICLES WILL BE OPERATED IN THE |
| | ENCLOSED TRUCK BAYS. HOW WILL CARBON MONOXIDE LEVELS BE |
| | MAINTAINED BELOW ACCEPTABLE THRESHOLDS PER 502.14 M? |
| | |
| | VOLUME 6 REVIEW: |
| | |
| | VOLUME 7 REVIEW: |
| | SHEET FP-DEW-04: PER FBC SECTION 905.1, A CLASS I |
| | STANDPIPE SYSTEM SHALL BE PROVIDED IN ALL NEW BUILDINGS |
| | IN WHICH THE HIGHEST FLOOR IS MORE THAN 30 FEET ABOVE |
| | FIRE DEPARTMENT VEHICLE ACCESS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |