| Date |
Text |
| 2014-10-23 06:52:58 | 10/20/2014 |
| | PROJECT: WPB WATER RECLAMATION FACILITY |
| | PERMIT#: 14090256 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SUBMITTAL DRAWINGS ARE INCOMPLETE AND UNSIGNED. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS TO FBC |
| | 107.2.1 |
| | |
| | 2) INDICATE SIZE, TYPE AND BURIAL DEPTH OF GROUND LOOP |
| | CONDUCTOR AT DEWATERING BUILDING. NEC 250.50 |
| | |
| | 3) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED |
| | IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE |
| | OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT |
| | DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT |
| | REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. FBC |
| | 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | |
| | 4) WIND LOADS ON EVERY BUILDING OR STRUCTURE (LIGHT |
| | POLES) SHALL BE DETERMINED IN ACCORDANCE WITH CHAPTERS |
| | 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF THE |
| | ALTERNATE ALL HEIGHTS METHOD IN FBC SECTION 1609.6. |
| | WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| | DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT |
| | NORMAL TO THE SURFACE CONSIDERED. PROVIDE WIND LOA |
| | CALCULATIONS INCLUDING POLE TYPE, LENGTH AND LUMINAIRE |
| | TYPE AND QUANTITY. FBC SECTION 1609.6 |
| | |
| | 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR FIRE ALARM, SECURITY, CCTV, AND |
| | DATA/COM SYSTEM CABLING AS APPLICABLE. |
| | WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |