| Plan Review Notes For Permit 14090248 |
| Permit Number |
14090248 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-24 05:17:08 | 1) SUBMIT A SITE PLAN THAT SHOWS THE WATER AND SEWER | | | CONNECTIONS AND THE SIZE OF THE WATER SERVICE AND SEWER | | | CONNECTION.. THE POTABLE WATER SERVICE SHALL BE | | | PROTECTED AGAINST BACKFLOW PER THE 2010 FL. PLUMBING | | | CODE SEC.608. | | | 2) INDICATE ON THE PLANS WHAT THE BUOLDING WILL BE USED | | | FOR. THE PLANS NOTE "BUSINESS OCCUPANCY". PLEASE BE | | | MORE SPECIFIC. WPB AMENDMENTS TO 2010 FBC SEC. 107.2.1. | | | 3) A DRINKING FOUNTAIN ( HI-LO) IS REQUIRED IN THE | | | BUILDING PER TABLE 403.1 OF 2010 FPC. | | | 4) SUBMIT 2 COPIES OF THE PLANS FOR REVIEW. WPB AMEND. | | | TO 2010 FBC SEC.107.1. | | | 5) PLANS SHOW 2" FIXTURE DRAIN FOR THE WATER | | | CLOSETS.THE MIN. SIZE FIXTURE DRAIN FOR A WATER CLOSET | | | IS 3" PER TABLE 709.1. | | | 6) SHT. 3 OF 5 SHOWS 1/2" VENTS THROUGH THE ROUGH. | | | CLARIFY. THE MIN. SIZE VTR IS 1 1/4". | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|