2014-09-24 05:17:081) SUBMIT A SITE PLAN THAT SHOWS THE WATER AND SEWER
 CONNECTIONS AND THE SIZE OF THE WATER SERVICE AND SEWER
 CONNECTION.. THE POTABLE WATER SERVICE SHALL BE
 PROTECTED AGAINST BACKFLOW PER THE 2010 FL. PLUMBING
 CODE SEC.608.
 2) INDICATE ON THE PLANS WHAT THE BUOLDING WILL BE USED
 FOR. THE PLANS NOTE "BUSINESS OCCUPANCY". PLEASE BE
 MORE SPECIFIC. WPB AMENDMENTS TO 2010 FBC SEC. 107.2.1.
 3) A DRINKING FOUNTAIN ( HI-LO) IS REQUIRED IN THE
 BUILDING PER TABLE 403.1 OF 2010 FPC.
 4) SUBMIT 2 COPIES OF THE PLANS FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC.107.1.
 5) PLANS SHOW 2" FIXTURE DRAIN FOR THE WATER
 CLOSETS.THE MIN. SIZE FIXTURE DRAIN FOR A WATER CLOSET
 IS 3" PER TABLE 709.1.
 6) SHT. 3 OF 5 SHOWS 1/2" VENTS THROUGH THE ROUGH.
 CLARIFY. THE MIN. SIZE VTR IS 1 1/4".
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692