| Plan Review Notes For Permit 14090248 |
| Permit Number |
14090248 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-22 07:44:51 | DATE: 9/22/2014 | | | PROJECT: RINKER ATHLETIC | | | PERMIT#: 14090248 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) TWO SIGNED SEALED SETS REQUIRED. | | | | | | 2) PROVIDE A SITE PLAN, ELECTRICAL SERVICE RISER, AND | | | LOAD CALCULATION. INCLUDE THE SIZE, TYPE, GROUNDING | | | DETAILS, WHERE IT IS BEING FED FROM AND THE LOCATION OF | | | THE UTILITY SOURCE AND THE LOCATION OF THE SERVICE | | | DISCONNETING MEANS RELATIVE TO THE MODULAR SITE. WPB | | | AMENDMENTS TO FBC 107.3.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|