| 2014-09-06 13:24:14 | DATE: 9/6/2014 |
| | PROJECT: AVACODO GRILL |
| | PERMIT#: 14060973 REVISION #14090187 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW ON REVISION #14090187 |
| | ACTION: DENIED |
| | |
| | 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1 THE PLAN IS NOT SIGNED BY THE DESIGNER |
| | OF RECORD. |
| | |
| | 2) THE SHEET NUMBER DOES NO COINCIDE WITH THE SHEET |
| | NUMBER ON THE PERMIT SET. THE SHEET #A5 ON THE PERMIT |
| | SET IS THE PLUMBING PLAN. THE ELECTRICAL PLAN IS ON |
| | SHEET #A4. REVISE THE SHEET NUMBER TO COINCIDE WITH THE |
| | APPROVED PERMIT SET. |
| | |
| | 3) THERE IS NO LOW VOLTAGE DATA CABLING SHOWN ON THE |
| | MASTER PERMIT SET. A SEPARATE PERMIT APPLICATION |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND |
| | SHOP DRAWINGS FOR ANY AND ALL OF THE FOLLOWING: POS |
| | SYSTEM, FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK, |
| | STRUCTURED CABLING, AUDIO(SPEAKERS)/VIDEO, AND SIGNAGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |