2014-10-11 12:17:45APPROVED WITH EXCEPTION.
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 1) NEC 210.52(E) OUTDOOR OUTLETS. (3) BALCONIES, DECKS
 AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE
 DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK OR
 PORCH. THE RECEPTACLE SHALL BE LOCATED NOT MORE THAN
 6.5 FT ABOVE THE BALCONY, DECK OR PORCH SURFACE.
  
  