Plan Review Notes
Plan Review Notes For Permit 14090135
Permit Number 14090135
Review Stop P
Sequence Number 2
Notes
Date Text
2014-10-02 07:49:021) 2ND REQUEST - SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THE HIBACHI TABLE. THE TABLES SHALL BE LISTED AND
 LABELED PER THE 2010 FLORIDA FUEL GAS CODE SEC. 301.3.
 THE SHEETS THAT WERE SUBMITTED DO NOT SHOW THAT THE
 TABLES ARE LISTED AND LABELED.
 2) YOU HAVE ADDED A TABLE ABOVE THE GAS RISER THAT
 READS "IRON PIPE SIZE". WHAT IS THE REASON FOR THIS
 TABLE?
 3) SUBMIT TWO COPIES OF THE APPLICABLE GAS SIZING
 TABLES THAT ARE BEING USED FOR THIS PROJECT.
 4) SHT. P-1 - I HAVE REFERENCED THE 2010 EDITION
 FLORIDA FUEL GAS CODE IN MY REVIEW COMMENTS AND YOU
 HAVE REFERENCED THE 2006 IFGC. REVISE THE NOTE TO
 COMPLY W/ THE 2010 FLORIDA FUEL GAS CODE.
 5) YOUR RESPONSE TO MY FIRST REVIEW COMMENT #5 REFERS
 TO FLEXIBLE GAS PIPING WITH A POLYETHYLENE SLEEVE. THIS
 DOES NOT SATISY THE REQUIREMENT FOR CONDUIT. COMPLY
 WITH THE 2010 FLORIDA FUEL GAS CODE 404.12.2. TRACPIPE
 ALSO REQUIRES THE CONDUIT. YOUR RESPONSE REFERS TO
 'SUBMITTED ATTACHMENT." THERE WAS NO ATTACHMENT FOR
 TRACPIPE.
 6) SHOW THE LENGTH OF EACH SECTION OF TRACK PIPEON THE
 PLAN AND THE RISER.
 7) SUBMIT THE CORRESPONDING EHD NUMBER FOR THE TRAC
 PIPE FROM THE APPLICABLE SIZING TABLE BEING USED.
 8) PLEASE SHOW THE SIZE OF THE EXISTING GREASE TRAP.
 9) CLARIFY THE SIZE OF THE WATER HEATER. THE PLAN SHOWS
 "7 I". CLARIFY.
 10) INDICATE ON THE PLAN WHAT WILL BE THE USE OF THE
 TWO ADDED SINKS?