| Plan Review Notes For Permit 14090135 |
| Permit Number |
14090135 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-19 14:27:38 | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | | HIBACHI TABLES. THE TABLES SHALL BE LISTED AND LABELED | | | PER THE 2010 FLORIDA GAS CODE 301.3. | | | 2) THE ADDED GAS LOAD FOR THE HIBACHI TABLES HAS NOW | | | MADE THE ENTIRE GAS SYSTEM UNDERSIZED. THE GAS SYSTEM | | | SIZING SHALL COMPLY WITH TABLE 402.4 (2) AS SPECIFIED | | | ON THE PLANS FOR A TOTAL RUN OF 128 FT. IF YOU INCREASE | | | THE GAS PRESSURE TO A 2 PSI SYSTEM AND SIZE THE SYSTEM | | | TO TABLE 402.4 (30 YOU WILL BE IN COMPLIANCE. | | | 3)SHT. P-2 - THE 3" WASTE LINE WITH THE AIR ADMITTANCE | | | VALVES FROM THE HAND SINKS TO THE EXISTING GREASE TRAP | | | REQUIRES A VENT TO THE OPEN AIR PER THE 2010 FBCP | | | SEC.917.7. THE VENT COULD BE INSTALLED AGAINST THE | | | EXTERIOR WALL ON THE OUTSIDE OF THE BUILDING TO COMPLY | | | WITH THIS CODE SECTION. | | | 4) IDENTIFY THE SQUARE ON THE GAS PIPING DIAGRAM WITH | | | THE LETTERS "GS" IN IT. | | | 5) GAS PIPING UNDER THE SLAB TO THE HIBACHI TABLES | | | SHALL BE ENCASED IN CONDUIT PER THE 2010 FBCG | | | SEC.404.12.2. SUBMIT A DETAIL FOR THIS INSTALLATION | | | SHOWING THE SIZE OF THE CONDUIT. THE CONDUIT SHALL | | | TERMINATE IN AN ACCESSIBLE PORTION OF THE BUILDING. | | | 6) SUBMIT A SANITARY AND WATER RISER FOR THE PLUMBING | | | WORK TO BE DONE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|