Plan Review Notes
Plan Review Notes For Permit 14090135
Permit Number 14090135
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-19 14:27:38WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 HIBACHI TABLES. THE TABLES SHALL BE LISTED AND LABELED
 PER THE 2010 FLORIDA GAS CODE 301.3.
 2) THE ADDED GAS LOAD FOR THE HIBACHI TABLES HAS NOW
 MADE THE ENTIRE GAS SYSTEM UNDERSIZED. THE GAS SYSTEM
 SIZING SHALL COMPLY WITH TABLE 402.4 (2) AS SPECIFIED
 ON THE PLANS FOR A TOTAL RUN OF 128 FT. IF YOU INCREASE
 THE GAS PRESSURE TO A 2 PSI SYSTEM AND SIZE THE SYSTEM
 TO TABLE 402.4 (30 YOU WILL BE IN COMPLIANCE.
 3)SHT. P-2 - THE 3" WASTE LINE WITH THE AIR ADMITTANCE
 VALVES FROM THE HAND SINKS TO THE EXISTING GREASE TRAP
 REQUIRES A VENT TO THE OPEN AIR PER THE 2010 FBCP
 SEC.917.7. THE VENT COULD BE INSTALLED AGAINST THE
 EXTERIOR WALL ON THE OUTSIDE OF THE BUILDING TO COMPLY
 WITH THIS CODE SECTION.
 4) IDENTIFY THE SQUARE ON THE GAS PIPING DIAGRAM WITH
 THE LETTERS "GS" IN IT.
 5) GAS PIPING UNDER THE SLAB TO THE HIBACHI TABLES
 SHALL BE ENCASED IN CONDUIT PER THE 2010 FBCG
 SEC.404.12.2. SUBMIT A DETAIL FOR THIS INSTALLATION
 SHOWING THE SIZE OF THE CONDUIT. THE CONDUIT SHALL
 TERMINATE IN AN ACCESSIBLE PORTION OF THE BUILDING.
 6) SUBMIT A SANITARY AND WATER RISER FOR THE PLUMBING
 WORK TO BE DONE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  