2014-09-22 10:15:43M-1, (1) THERE ARE 3 BATH FANS INDICATED ON THE AIR
 BALANCE CHART, PROVIDE LOCATION OF 3RD BATH.
 (2) THERE ARE A TOTAL OF 5 MUA FANS ON THE DRAWING,
 THERE ARE 6 ON THE AIR BALANCE CHART ?
 (3) AGAIN THE AIR BALANCE CHART INDICATES 10 TEPPAN
 YAKI EXHAUST FANS, ONLY 8 ARE SHOWN?
 (4) MUA DUCT AND FANS ARE SHOWN BETWEEN THE TEPPAN YAKI
 HOODS BUT ARE REMOTE TO THE EXHAUST ON THE ROOF,
 INDICATE DUCT AND SIZES
 AND ROUTING ON PLANS.
 (5) WILL THE MUA UNIT(S) PROVIDE 100% OF THEIR CAPACITY
 IF ONLY ONE TEPPAN YAKI GRILL IS IN OPERATION OR IS IT
 A TWO SPEED STAGGED OPERATION
 (6) PROVDE PARAPET WALL HEIGHT BEHIND MAIN HOOD OR
 STRUCTURAL RAILING DETAIL
 M-2 (1) PROVIDE DETAIL OF GREASE DUCT PENETRATION THRU
 CEILIN, WOOD TRUSSES AND ROOF ASSEMBLY (NFPA 96)
  