| Plan Review Notes For Permit 14090135 |
| Permit Number |
14090135 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-22 10:15:43 | M-1, (1) THERE ARE 3 BATH FANS INDICATED ON THE AIR | | | BALANCE CHART, PROVIDE LOCATION OF 3RD BATH. | | | (2) THERE ARE A TOTAL OF 5 MUA FANS ON THE DRAWING, | | | THERE ARE 6 ON THE AIR BALANCE CHART ? | | | (3) AGAIN THE AIR BALANCE CHART INDICATES 10 TEPPAN | | | YAKI EXHAUST FANS, ONLY 8 ARE SHOWN? | | | (4) MUA DUCT AND FANS ARE SHOWN BETWEEN THE TEPPAN YAKI | | | HOODS BUT ARE REMOTE TO THE EXHAUST ON THE ROOF, | | | INDICATE DUCT AND SIZES | | | AND ROUTING ON PLANS. | | | (5) WILL THE MUA UNIT(S) PROVIDE 100% OF THEIR CAPACITY | | | IF ONLY ONE TEPPAN YAKI GRILL IS IN OPERATION OR IS IT | | | A TWO SPEED STAGGED OPERATION | | | (6) PROVDE PARAPET WALL HEIGHT BEHIND MAIN HOOD OR | | | STRUCTURAL RAILING DETAIL | | | M-2 (1) PROVIDE DETAIL OF GREASE DUCT PENETRATION THRU | | | CEILIN, WOOD TRUSSES AND ROOF ASSEMBLY (NFPA 96) | | | |
|