| Plan Review Notes For Permit 14090135 |
| Permit Number |
14090135 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-16 14:56:59 | 14090135 | | | 6901 OKEECHOBEE BLVD #81 | | | RESTAURANT REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | THE TOTAL SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR. | | | ARE THE PANELS NEW OR EXISTING? SHOW ALL NEW CIRCUITS | | | AND OUTLETS. PROVIDE AN ELECTRICAL RISER SHOWING | | | EXISTING AND NEW WORK ANDLOCATION OF MAIN SERVICE | | | DISCONNECTS. NEC 215.5 | | | | | | VERIFY A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS HAS BEEN PROVIDED. NEC 110.16, | | | 110.22 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN | | | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; | | | 505.5.3; T. 505.5.3 | | | | | | PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5 | | | | | | CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING | | | CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE | | | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL | | | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME | | | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST | | | 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE | | | BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2 | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | | | | | | | |
|