Plan Review Notes
Plan Review Notes For Permit 14090135
Permit Number 14090135
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-16 14:56:5914090135
 6901 OKEECHOBEE BLVD #81
 RESTAURANT REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE TOTAL SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR.
 ARE THE PANELS NEW OR EXISTING? SHOW ALL NEW CIRCUITS
 AND OUTLETS. PROVIDE AN ELECTRICAL RISER SHOWING
 EXISTING AND NEW WORK ANDLOCATION OF MAIN SERVICE
 DISCONNECTS. NEC 215.5
  
 VERIFY A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS HAS BEEN PROVIDED. NEC 110.16,
 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE
 BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  
  