2014-09-15 14:21:37DATE: 9/15/2014
 PROJECT: RIVERWALK RESORT POOL HEATERS.
 PERMIT#: 14090122
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE
 FPL TRANSFORMER AND THE ELECTRICAL SERVICE EQUIPMENT.
 WPB AMENDMENTS TO FBC 107.2.1
  
 2) A GROUNDING ELECTRODE SYSTEM IS REQUIRED. PROVIDE A
 GROUNDING ELECTRODE SYSTEM DETAIL AS OUTLINED IN THE
 NEC 250.50
  
 3) PROVIDE A LOAD CALCULATION AND A PANEL SCHEDULE FOR
 THE 200AMP PANEL AND A PANEL SCHEDULE FOR THE 100AMP
 PANEL INCLUDE ALL BREAKER TYPES AND SIZES.
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  