| Plan Review Notes For Permit 14090114 |
| Permit Number |
14090114 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-30 10:48:59 | 9/30/2014 | | | PROJECT: SERVICE CHANGE + SMOKE DETECTORS. | | | PERMIT#: 14090114 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE PANEL SCHEDULE FOR NEW 200AMP. MB PANEL. WPB | | | AMENDMENTS TO FBC 107.3.2 | | | | | | 2) PROVIDE SIZE OF GROUNDING ELECTRODE CONDUCTOR. NEC | | | 250.66 | | | | | | 3) PROVIDE MULTI-SYSTEM BONDING STRIP AT GROUNDING | | | ELECTRODE SYSTEM. NEC 250.94 | | | | | | 4) PROVIDE FLOOR PLAN TO INDICATE LOCATION OF SMOKE | | | DETECTORS IN COMPLIANCE WITH FBC 314-315 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|