| Notes |
| Date |
Text |
| 2014-09-15 11:24:04 | DATE: 9/15/2014 | | | PROJECT: APT-GARAGE CONVERSION | | | PERMIT#: 14090059 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) | | | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION | | | FOR PERSONNEL. ALL OUTLETS IN THE GARAGE INCLUDING THE | | | GDO OUTLETS SHALL BE GFCI PROTECTED. NEC 210.8. | | | | | | 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | | 314 AND 315. VERIFY OR INSTALL SMOKE/CO DETECTORS ARE | | | INSTALLED IN THE APT ON THE SECOND FL. FBC-R 314, 315 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|