| 2014-09-06 07:08:50 | 1) SHT.G0-1 - ACCESSIBILITY NOTE #2 - THE SIDE REACH |
| | RANGES SHALL COMPLY W/ THE FLORIDA ACCESSIBILITY CODE |
| | SEC.308.3 THRU 308.3.2. |
| | 2) CLOTHES RODS SHALL COMPLY W/THE REACH RANGES IN |
| | SECS.308.1 & 803.5 2010 FAC. |
| | 3) SHT. A1-1 - THE NEW SAUNA, RESTROOMS AND SHOWES |
| | SHALL COMPLY W/ THE 2010 FAC SEC.213.2 & SEC. 603, |
| | SEC.612, 903, 903.2, AND 304. |
| | 4) SHOW THE FIXTURE CLEARANCES FOR THE WATER CLOSETS IN |
| | ACCORDANCE W/ THE 2010 FAC SEC. 604.2. |
| | 5) SHT.A1-1 - HOW CAN THE RESTROOMS # 101 & 102 BE |
| | EXISTING WHEN THESE ROOMS ARE NOT SHOWN ON G1-1 & THE |
| | PARTITIONS ARE SHOWN AS NEW? WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 6) SUBMIT ACCESSIBILITY DETAILS (ELEVATIONS) FOR THE |
| | PLUMBING FIXTURES, GRAB BARS,SHOWER SEAT, ETC. WPB |
| | ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. |
| | 7) DOORS SHALL NOT SWING INTO THE REQUIRED FLOOR SPACE |
| | REQUIRED FOR ANY FIXTURE OER 2010 FAC SEC.603.2.3. ( |
| | SEE EXCEPTIONS). SHOW THE REQUIRED CLEAR FLOOR SPACE |
| | FOR THE WATER CLOSETS AND THE LAVATORIES AND THE SHOWER |
| | AND SAUNA. |
| | 8) THE SEAT AND CONTROLS IN THE SHOWER SHALL COMPLY W/ |
| | FAC SEC.608.2.3, 608.5.3. 608.6 , 610.1., 610.3. |
| | 9) SUBMIT A WATER RISER DIAGRAM FOR THE |
| | CHANGES/ADDITTIONS BEING MADE TO THE POTABLE WATER |
| | SYSTEM. |
| | 10) SHT. P1-1 - SIZE ALL SECTIONS OF THE SANITARY RISER |
| | INCLUDING THE EXISTING. |
| | 11) THE MINIMUM SLOPE ON THE DRAINAGE PIPING SHALL |
| | COMPLY W/ TABLE 704.1 OF THE 2010 FLORIDA PLUMBING CODE |
| | DEPENDING ON THE PIPE SIZE. SEE NOTE #4 ON P1-1 UNDER |
| | "PLUMBING NOTES". |
| | 12) FLORIDA PLUMBING CODE SEC. 909.2.1.- NOT MORE THAN |
| | ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM |
| | OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE- |
| | CHIEF PLUMBING INSPECTOR |
| | TEL:561-805-6692 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |