| Plan Review Notes For Permit 14090024 |
| Permit Number |
14090024 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-09-28 12:42:04 | PROVISO: | | | | | | THE BREAKER SIZES SPECIFIED ON THE PANEL SCHEDULE ARE | | | NOT THE SAME AS ON THE A/C SHEET FOR THE AHU & | | | CONDENSER. PLEASE ADVISE IF YOU WOULD LIKE TO RESOLVE | | | THIS AS A REVISION LATER, OR A RE-SUBMITTAL PRIOR TO | | | ISSUANCE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|