| Plan Review Notes For Permit 14090024 |
| Permit Number |
14090024 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-10 14:01:49 | 1ST REVIEW: FBC 2010 | | | | | | FBC- 107.3.5.3 - PROVIDE A LARGER, MORE LEGIBLE | | | MECHANICAL PLAN TO SHOW SUPPLY DUCTS PER FBC-R M16 & | | | BATH EXHAUST PER FBC-R M15. | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|