2014-09-02 16:45:22DATE: 9/2/2014
 PROJECT: 918 30TH ST
 PERMIT#: 14090024
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) IT APPEARS BY WHAT IS INDICATED ON THE PLANS THE
 ELECTRICAL PANEL IS LOCATED IN THE KITCHEN UTILITY
 CLOSET BEHIND WASHER/DRYRER. THE ELECTRICAL PANEL
 REQUIRES CLEAR UNOBSTRUCTED WORKING ACCESS. NEC 110.26.
 REVVISE PLANS FOR CODE COMPLIANCE.
  
 2) ONE GFI RECEPTACLE IS REQUIRED WITHIN SIGHT OF
 MECHANICAL EQUIPMENT. REVISE PLANS TO INDICATE REQUIRED
 OUTLETS BY MECHANICAL EQUIPMENT. NEC 210.63 SEE
 210.8(A)(3),
  
 3) SMOKE/CO DETECTORS ARE REQUIRED PER THE FBC-R 314,
 315. IDENTIFY THE REQUIRED SMOKE DETECTORS.
 FBC-RESIDENTIAL 314.3 AND 314.3.1
  
 4) PROVIDE A RISER DIAGRAM, PANEL SCHEDULE, LOAD
 CALCULATION AND SITE PLAN TO INDICATE THE LOCATION OF
 THE ELECTRICAL SERVICE AND MAIN DISCONNECT FBC 107.2.1,
 NEC 230.70
  
 5) TWO SETS OF PLANS AND SPECIFICATIONS ARE REQUIRED
 FOR REVIEW. WPB FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  