| 2014-09-02 16:45:22 | DATE: 9/2/2014 |
| | PROJECT: 918 30TH ST |
| | PERMIT#: 14090024 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) IT APPEARS BY WHAT IS INDICATED ON THE PLANS THE |
| | ELECTRICAL PANEL IS LOCATED IN THE KITCHEN UTILITY |
| | CLOSET BEHIND WASHER/DRYRER. THE ELECTRICAL PANEL |
| | REQUIRES CLEAR UNOBSTRUCTED WORKING ACCESS. NEC 110.26. |
| | REVVISE PLANS FOR CODE COMPLIANCE. |
| | |
| | 2) ONE GFI RECEPTACLE IS REQUIRED WITHIN SIGHT OF |
| | MECHANICAL EQUIPMENT. REVISE PLANS TO INDICATE REQUIRED |
| | OUTLETS BY MECHANICAL EQUIPMENT. NEC 210.63 SEE |
| | 210.8(A)(3), |
| | |
| | 3) SMOKE/CO DETECTORS ARE REQUIRED PER THE FBC-R 314, |
| | 315. IDENTIFY THE REQUIRED SMOKE DETECTORS. |
| | FBC-RESIDENTIAL 314.3 AND 314.3.1 |
| | |
| | 4) PROVIDE A RISER DIAGRAM, PANEL SCHEDULE, LOAD |
| | CALCULATION AND SITE PLAN TO INDICATE THE LOCATION OF |
| | THE ELECTRICAL SERVICE AND MAIN DISCONNECT FBC 107.2.1, |
| | NEC 230.70 |
| | |
| | 5) TWO SETS OF PLANS AND SPECIFICATIONS ARE REQUIRED |
| | FOR REVIEW. WPB FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |