Plan Review Notes
Plan Review Notes For Permit 14090005
Permit Number 14090005
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-02 14:01:12DATE: 9/2/2014
 PROJECT: MARRIOTT RESIDENCE INN. SITE LIGHTING
 PERMIT#: 14090005
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE LOCATION OF ELECTRICAL PANEL TO SERVE THE
 SITE LIGHTING LOAD,
  
 2) PROVIDE A PANEL SCHEDULE INDICATING THE NEW
 CIRDCUIT(S) AND A LOAD CALCULATION INDICTING THE NEW
 LOAD.
  
 2) INCICATE COMPLIANCE WITH THE FLORIDA BUILDING CODE
 FOR ENERGY CONSERVATION. FBC-E 505.2.4
  
 3) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP
 DRAWINGS AS REQUIRED FOR GATE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  