Plan Review Notes
Plan Review Notes For Permit 14081301
Permit Number 14081301
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-02 16:34:45FBC 2010, 1ST REVIEW:
  
 PROVIDE A COMPLETE ELECTRICAL PLAN PER THE SCPOE OF
 WORK DESCRIBED ON THE ELECTRICAL PERMIT APPLICATION AS
 FOLLOWS:
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
  
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 7.5? OF MECHANICAL EQUIPMENT.
  
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
 NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED
 BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  