| 2014-09-08 17:30:56 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | MECHANICAL |
| | |
| | 1) THE ENERGY FORM 402-2010 THAT WAS SUBMITTED APPEARS |
| | TO CONTAIN SO ERRORS. PLEASE CORRECT. |
| | - THE CONDITIONED AREA IS LISTED AS 1040 SQFT AND THE |
| | CEILING AREA IS LISTED AS 537 SQFT. |
| | - THE AIR HANDLER UNIT LOCATION IS SPECIFIED AS THE |
| | GARAGE. THIS PLANS SHOWS THE UNIT IN A HALL CLOSET. THE |
| | PLAN DOES NOT SHOW A GARAGE. |
| | - THE SEER IS LISTED AS 16 ON THE FORM AND THE AHRI |
| | CERTIFICATION THAT WAS SUBMITTED HAS A SEER RATING OF |
| | 13. |
| | |
| | 2) THE EQUIPMENT SIZING CALCULATIONS SPECIFY THE TOTAL |
| | COOLING REQUIRED IS 27,082 BTUH OR 2.26 TONS. THE A/C |
| | CHANGE OUT FORM AND THE AHRI CERTIFICATION FORM ARE FOR |
| | A 3 TON SYSTEM. BASED ON THE SIZING CALCULATIONS AND |
| | FBC ENERGY CONSERVATION SEC. 403.6.1.1, THE MAXIMUM |
| | COOLING EQUIPMENT SIZE IS |
| | 403.6.1.1 COOLING EQUIPMENT CAPACITY. |
| | COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS |
| | TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL |
| | LOAD BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE |
| | TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE |
| | SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE |
| | SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE |
| | CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL |
| | NOT BE LESS THAN THE CALCULATED LATENT LOAD. |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |