| 2014-11-26 11:07:19 | DATE: 11/26/14 |
| | PROJECT: MIZNER LAKES, SITE LIGHTING |
| | PERMIT#: 14081250 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NOTE 5 ON SHEET E1.2 CALLS FOR A DETAIL ON SHEET |
| | E2.1. PROVIDE SHEET E2.1 FOR REVIEW. |
| | |
| | 2) PROVIDE A PANEL SCHEDULE INDICATING THE SYSTEM |
| | VOLTAGE, THE SIZE OF THE MAIN OCPD, AIC RATING, AND |
| | IDENTIFY EACH INDIVIDUAL CIRCUIT FOR THE LIGHTING ON |
| | THE PLAN. |
| | |
| | 3) PROVIDE A LOAD CALCULATION INDICATING THE TOTAL |
| | CONNECTED LOAD ON THE WHOLE PANEL INCLUDING THE |
| | ADDITIONAL LOAD OF THE NEW SITE LIGHTING. IF THERE ARE |
| | MULTIPLE PANELS COMPLETE FOR EACH PANEL. |
| | |
| | 4) PROVIDE AND INDICATE ON THE PLANS THE WIRING METHOD, |
| | VOLTAGE, AMPERAGE, SIZE OF BRANCH CIRCUIT OCPD, CONDUIT |
| | AND WIRE SIZE, AS WELL AS LIGHTING CONTROL AS REQUIRED |
| | IN THE FBC SECTION 505.2.4 |
| | |
| | 5) PROVIDE ADDITIONAL DETAIL REAGARDING THE |
| | INSTALLATION OF THE IRRIGATION SYSTEMS AND FOR THE |
| | FLOATING FOUNTAINS. PROVIDE DETAILS THAT PROVIDE |
| | COMPLIANCE WITH THE NEC 682 AND 430 |
| | |
| | 6) COMPLY WITH THE NOTES ADDED BY JULIO GOMEZ BUILDING |
| | REVIEWER REGARDING THE ENGINEERING FOR WIND LOAD AND |
| | THE CHANGE OF ENGINEER. IF LUIS VARGAS OF POWER DESIGN |
| | IS TAKING OVER THE DESIGN OF THE DESIGN |
| | RESPONSABILITIES OF THE SITE LIGHTING PROJECT HIS |
| | ORIGINAL SEAL AND SIGNATURE MUST APPEAR ON ALL SHEETS |
| | SUBMITTED FOR REVIEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |