| 2014-08-29 11:06:38 | SENT TO ZONING FOR PHOTOMETRIC REVIEW |
| 2014-08-29 11:03:31 | DATE: 8/29/2014 |
| | PROJECT: MIZNER LAKES, SITE LIGHTING |
| | PERMIT#: 14081250 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE AND INDICATE ON THE PLANS, THE LOCATION OF |
| | THE SOURCE OF POWER, CONDUIT ROUTING, BURIAL DEPTH, |
| | CIRCUIT #'S, AND GROUNDING DETAIL. PROVIDE VOLTAGE DROP |
| | CALCULATIONS AS NEEDED. IF THERE ARE MULIPLE SOURCES |
| | INDICATE EACH ONE INDIVIDUALLY AND COMPLETE THE REST OF |
| | THE DETAIL FROM EACH INDIVIDUAL SOURCE. |
| | |
| | 2) PROVIDE A PANEL SCHEDULE INDICATEING THE SYSTEM |
| | VOLTAGE, THE SIZE OF THE MAIN OCPD, AIC RATING, AND |
| | IDENTIFY EACH INDIVIDUAL CIRCUIT FOR THE LIGHTING ON |
| | THE PLAN. |
| | |
| | 3) PROVIDE A LOAD CALCULATION INDICATING THE TOTAL |
| | CONNECTED LOAD ON THE WHOLE PANEL INCLUDING THE |
| | ADDITIONAL LOAD OF THE NEW SITE LIGHTING. IF THERE ARE |
| | MULTIPLE PANELS COMPLETE FOR EACH PANEL. |
| | |
| | 4) PROVIDE AND INDICATE ON THE PLANS THE METHOD OF |
| | LIGHTING CONTROL AS REQUIRED IN THE FBC SECTION 505.2.4 |
| | AGAIN IF THERE ARE MULTIPLE SOURCES COMPLETE FOR EACH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |