Plan Review Notes
Plan Review Notes For Permit 14081231
Permit Number 14081231
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-19 11:15:171) THE FLOOR PLAN SHOWS ONE DRINKING FOUNTAIN. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. 2010 FL.
 ACCESS. CODE SEC. 211.2.
 2) SHOW THE SIZE OF THE FLOOR DRAIN/PIPING. WPB ADMIN.
 AMEND. TP 2010 FBC SEC. 107.2.1.
 3) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 4) SHT. P-1 - THE WATER HEATER DETAIL SHOWS THE RELIEF
 LINE DISCHARGING TO A FLOOR DRAIN BUT THERE IS NO FLOOR
 DRAIN LOCATED IN THE ROOM. CLARIFY.
 5) THE DRAINAGE SYSTEM SHALL HAVE ONE VENT STACK OR
 STACK VENT THAT EXTENDS OUTDOORS TO THE OPEN AIR PER
 THE 2010 FPC SEC.917.7.
 6) SHT. P-1, NOTE #1 STATES "3/4" DIRECT WASTE TO
 PEDICURE CHAIRS.TYPICAL OF TWO." WHAT IS THIS NOTE
 REFERRING TO? THE SPEC SHEETS FOR THE CHAIRS SHOW AN 1
 1/2" DRAIN. CLARIFY.
 7) SHOW THE SIZE OF THE VENT FOR THE LAVATORY.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  