| Plan Review Notes For Permit 14081231 |
| Permit Number |
14081231 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-19 11:15:17 | 1) THE FLOOR PLAN SHOWS ONE DRINKING FOUNTAIN. NO FEWER | | | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. 2010 FL. | | | ACCESS. CODE SEC. 211.2. | | | 2) SHOW THE SIZE OF THE FLOOR DRAIN/PIPING. WPB ADMIN. | | | AMEND. TP 2010 FBC SEC. 107.2.1. | | | 3) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1. | | | 4) SHT. P-1 - THE WATER HEATER DETAIL SHOWS THE RELIEF | | | LINE DISCHARGING TO A FLOOR DRAIN BUT THERE IS NO FLOOR | | | DRAIN LOCATED IN THE ROOM. CLARIFY. | | | 5) THE DRAINAGE SYSTEM SHALL HAVE ONE VENT STACK OR | | | STACK VENT THAT EXTENDS OUTDOORS TO THE OPEN AIR PER | | | THE 2010 FPC SEC.917.7. | | | 6) SHT. P-1, NOTE #1 STATES "3/4" DIRECT WASTE TO | | | PEDICURE CHAIRS.TYPICAL OF TWO." WHAT IS THIS NOTE | | | REFERRING TO? THE SPEC SHEETS FOR THE CHAIRS SHOW AN 1 | | | 1/2" DRAIN. CLARIFY. | | | 7) SHOW THE SIZE OF THE VENT FOR THE LAVATORY. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|